The LSZ three-phase integrated current transformer is suitable for installation on the three-phase bushing ring of the switchgear and the main column switch for the measurement and protection of three-phase current and zero-sequence current. It can also be used for multiple cable circuits. Measurement and protection of zero sequence current.
The iron core and secondary winding of the series of zero-sequence current transformers are vacuum casted in a flame-retardant plastic housing with high-quality epoxy resin, which is moisture-proof, stable in performance and maintenance-free.
Technical Parameters:
|
Conditions of Use:
|
Current Transformer frequency: 50Hz or 60Hz;,
|
Ambient temperature: -35 ° C - +55 ° C
|
Current Transformer secondary current: 5A or 1A;
|
Average temperature: ≤ 40 ° C.
|
Power frequency withstand voltage 3kV, 1min;
|
Altitude: ≤3000m
|
Current Transformer expansion current: 120%In;
|
Atmosphericconditions: no serious pollution in the atmosphere
|
Implementation standards:GB1208-2006;
WNCB001-2008 (enterprise standard).
|
|
P2 represents the primary polarity end, and S1 and S2 represent the secondary polarity end; P2 and S2 are the same name end (reduced polarity).
|
|
Dimensions:
Model
|
M
(mm)
|
φ
(mm)
|
D
(mm)
|
H
(mm)
|
h
(mm)
|
L
(mm)
|
LSZ107-75
|
107
|
75
|
65
|
128
|
64
|
322
|
LSZ107-83
|
107
|
83
|
60
|
150
|
73.5
|
340
|
LSZ110-83
|
110
|
83
|
50
|
160
|
87.5
|
365
|
LSZ110-80
|
110
|
80
|
65
|
150
|
75
|
342
|
LSZ125-82
|
125
|
82
|
50
|
175
|
100
|
400
|
LSZ130-83
|
130
|
83
|
55
|
146.5
|
83.5
|
387
|
LSZ135-83(I)
|
135
|
83
|
57
|
184
|
100
|
440
|
LSZ135-83(II)
|
135
|
83
|
75
|
184
|
110
|
440
|
LSZ135-110
|
135
|
110
|
85
|
180
|
100
|
430
|
LSZ150-65
|
150
|
65
|
85
|
157
|
73.5
|
457
|
Rated current ratio, accuracy level and rated load table:
Model
|
LSZ series AC two phase
|
Use
|
Measuring current transformer
|
Protection current transformer
|
Double winding Current Transformer
|
Current ratio
I1/I2
|
Accuracy and rated load(VA)
|
Double windingAccuracy and rated load(VA)
|
0.5
|
1
|
3
|
10P15
|
10P10
|
10P5
|
0.5
|
1
|
10P10
|
10P5
|
100
|
2.5
|
|
|
|
1.5
|
3.75
|
|
|
|
|
150
|
3.75
|
|
|
|
2.5
|
5
|
|
|
|
|
200
|
5
|
|
|
|
2.5
|
7.5
|
2.5
|
|
|
2.5
|
300
|
7.5
|
|
|
|
3.75
|
10
|
2.5
|
|
2.5
|
5
|
400
|
10
|
|
|
2.5
|
5
|
15
|
2.5
|
|
2.5
|
7.5
|
500
|
10
|
|
|
2.5
|
5
|
15
|
2.5
|
|
3.75
|
10
|
600
|
10
|
|
|
2.5
|
7.5
|
20
|
5
|
|
3.75
|
10
|
800
|
10
|
|
|
2.5
|
7.5
|
20
|
5
|
|
5
|
15
|
Model
|
LSZ series three-phase
|
Use
|
Measuring current transformer
|
Protection current transformer
|
Double winding Current Transformer
|
Rated Current ratio
I1/I2
|
Accuracy and rated load(VA)
|
Double winding Accuracy and rated load(VA)
|
0.5
|
1
|
3
|
10P15
|
10P10
|
10P5
|
0.5
|
1
|
10P10
|
10P5
|
100
|
2.5
|
5
|
7.5
|
|
1.5
|
2.5
|
|
2.5
|
|
2.5
|
150
|
2.5
|
5
|
7.5
|
|
2.5
|
3.75
|
|
3.75
|
|
2.5
|
200
|
3.75
|
5
|
10
|
|
2.5
|
5
|
2.5
|
|
|
|
300
|
5
|
7.5
|
|
|
3.75
|
7.5
|
2.5
|
|
|
|
400
|
10
|
|
|
2.5
|
5
|
10
|
2.5
|
|
2.5
|
5
|
500
|
10
|
|
|
2.5
|
5
|
10
|
3.75
|
|
2.5
|
5
|
600
|
10
|
|
|
5
|
10
|
15
|
5
|
|
5
|
10
|
800
|
15
|
|
|
5
|
10
|
15
|
5
|
|
5
|
10
|
Model
|
LSZ series zero sequence
|
Use
|
Zero sequence Current Transformer
|
Rated Current ratio
I1/I2
|
Accuracy and Current Transformer load(VA)
|
3
|
10P
|
20/1
|
0.5
|
0.5
|
30/1
|
0.5
|
0.5
|
50/1
|
0.5
|
0.5
|
100/1
|
1
|
1
|
50/5
|
1.5
|
1.5
|
75/5
|
2.5
|
2.5
|
100/5
|
2.5
|
2.5
|
150/5
|
2.5
|
2.5
|
Current transformers with different specifications and parameters can be customized according to user requirements