Overview:
This type of voltage transformer is an
epoxy resin cast composite insulated, fully enclosed product, which is suitable
for voltage and electric energy measurement in power systems with rated
frequency of 50Hz and rated voltage of 10kV and below.
Technical parameters:
The product complies with the standard:
GB1207-2006 and IEC60044-2
Rated frequency: 50Hz
Ambient temperature: -35 ° C ~ +40 ° C
Pollution level: Level II
Model
|
Rated voltage
ratio (kV)
|
Rated frequency
|
Accuracy
|
Rated output
(VA)
|
Thermal limit
output (VA)
|
Rated insulation
level (kV)
|
JDZW-6R2G
|
6/√3/0.1√3/0.1/3
|
50,60
|
0.2/6P
|
15/50
|
200
|
7.2/32/60
|
0.5/6P
|
30/50
|
JDZW-10R2G
|
10/√3/0.1/√3/0.1/3
|
50,60
|
0.2/6P
|
15/50
|
200
|
12/42/75
|
0.5/6P
|
30/50
|
Appearance and
installation size: